system description
Design
The prefabricated gypsum board tile with integrated capillary tube mat is a joint development with our system partner Vogl Deckensysteme. The gypsum board tiles are inserted into commercially available
T-rails. On the visible side, there is a perforated or unperforated gypsum board grid ceiling for the removal or supply of sensitive heat loads. The water circulates noiselessly in the capillary tube mats and
regulates the room temperature largely by radiation, partly by convection.
Gypsum board ceiling tile & Capillary tube mat
The gypsum board ceiling tiles, surface finished in white, consists of a 12,5 mm unperforated or perforated gypsum board tile with 8/18 R perforation from our system partner Vogl (other hole patterns are available) and the Clina capillary tube mat OVAMAT
GB 15/GB 18.
Length & Width & Panel thickness
The gypsum board ceiling tiles are available in the dimensions 1.250 x 625 mm, 1.200 x 600 mm,
625 x 625 mm and 600 x 600 mm.
The ceiling tile thickness is 12,5 mm.
Hydraulic connection
The connections of the gypsum board ceiling tiles to each other as well as the connection to the supply and return lines/ceiling sub-distributors are made on site using a proven push-lock system with flexible hoses. Pipes and sub- distributors are accommodated in the void of the suspended ceiling.
Of course, the ceiling void can be used for further installations.
Mounting
The prefabricated gypsum board ceiling tiles are inserted into standard T-rails T15/T24.
Processing
According to the common rules of dry construction. Processing of inactive surfaces with 12,5 mm gypsum board ceiling tiles.
Lamps & Ventilation
Openings can be freely repositioned within the ceiling grid or by using inactive ceiling tiles.
Regulation
The system can be regulated room-by-room.
Fields of application
Suitable for the modern interior design of rooms with special acoustic requirements, such as office buildings or public buildings, whether new construction or renovation.
structure
The prefabricated gypsum board ceiling tiles are inserted into standard T-rails T15/T24. It is important to wear fabric gloves when inserting the ceiling tiles, as the surface is coated white at the factory. The ceiling tiles are reversible.
The connections of the gypsum board tiles to each other as well as the connection to the supply and return lines/ceiling sub-distributors are made on site using a proven push-lock system with flexible hoses.
Pipes and sub distributors are accommodated in the void of the suspended ceiling.
The ceiling void can be used for further installations.
prefabricated product
Parallel slots are milled into the rear side of a 12,5 mm gypsum board tile. With the perforated version 8/18 R at a distance of 18 mm and with the unperforated version at a distance of 15 mm.
The capillaries of the capillary tube mat OVAMAT GB 18 or GB 15, consisting of an oval mat distributor pipe (20 x 12 x 2,0 mm) and capillary tubes (4,3 x 0,8 mm), are inserted in these slots.
The centre-to-centre distance between the capillary tubes is 18 mm or 15 mm.
A black acoustic fleece is glued to the back of the perforated version over the entire surface, while the unperforated version has a cover paper.
advantages
Cooling and heating with one system
In most buildings, the heat requirement to be covered is so low due to the well-insulated building envelope that capillary tube mats invisibly integrated into the gypsum board ceiling not only provide excellent cooling in the summer, but can also be used to heat very comfortably and energy-efficiently in the cold season.
High degree of prefabrication
Factory prefabrication ensures quality, function and thermal performance.
Optimized acoustics
This ceiling design enables optimised room acoustics, as the acoustic values of the perforated gypsum board ceiling tiles remain unchanged.
Easy retrofitting
The gypsum board ceiling tiles can be inserted into an existing T-rail construction. The hydraulic connection is located in the ceiling void.
Simple combination of active and inactive ceiling tiles is possible. The grid ceiling is reversible.
Quick and easy installation
The hydraulic connection is made using a proven push-lock system.
The gypsum board ceiling tiles can completely be installed in the drywall work.
Insert, connect, ready!
Individual room control
The temperature can be regulated room-by-room.
values
HEATING CAPACITY according to DIN EN 14037/5 |
COOLING CAPACITA according to DIN EN 14240 |
ACOUSTICS (applies only to perforated version) |
85,1 W/m² 77,4 W/m² 71,5 W/m² |
71,8 W/m² 65,3 W/m² 60,3 W/m² |
weighted sound absorption coefficient up to αw = 0,7 (Class C) |
INSTALLTION HEIGHT: |
SYSTEM WEIGHT: |
PRESSURE STAGE: PN 10 |