prefabricated product| perforated/ unperforated gypsum board ceiling tile with integrated capillary tube mat OVAMAT GB 18/GB 15
GYPSUM BOARD CEILING TILE - PERFORATED  

Gipskartonkassette gelocht mit integrierter Clina Kapillarrohrmatte_1

Gipskartonkassette gelocht mit integrierter Clina Kapillarrohrmatte

PUSH-LOCK CONNECTIONS

DESIGNATION GYPSUM BOARD
CEILING TILE
DESCRIPTION with 2 push-lock connections on the left

ANGULAR POSITION
PUSH-LOCK CONNECTION

90°
PICTOGRAM OPTIPANEL (Standard) Piktogramm Anschlüsse
angular position push-lock connection 90° oval mat distributor pipe

angular position push-lock connection 90°
oval mat distributor pipe

FILEDS OF APPLICATION

  • gypsum board grid ceiling

TECHNICAL DATA

CAPILLARY TUBE MAT MATERIAL/COLOUR polypropylene (PP-R) recyclable/blue
MAT DISTRIBUTOR PIPE 20 x 12 x 2,0 mm, oval
CAPILLARY TUBE OF THE OVAMAT 4,3 x 0,8 mm
DISTANCE OF THE CAPILLARY TUBES 18 mm centre-to-centre distance (perforated version, standard hole pattern 8/18 R)
15 mm centre-to-centre distance (unperforated version)
GYPSUM BOARD CEILING TILE

unperforated or perforated
hole pattern
8/18 R (standard); 6/18 R, 12/25 R; 8/18 Q; 12/25 Q 
dull white surface finish, black acoustic fleece backing 

LENGTH x WIDTH FOR GRID 1.250 x 625 mm, 1.200 x 600 mm, 625 x 625 mm (standard),
600 x 600 mm; (standard hole pattern 8/18 R)
PANEL THICKNESS 12,5 mm
INSULATION MATERIAL with 30 mm CARUSO-ISO-BOND, WLG 040 acc. to ceiling tile dimensions
CONNECTION TYPE with 2 push-lock connections 10 mm, angular position 90°°
SPECIFIC VOLUME OF WATER 0,370 l/m² capillary tube surface
SPECIFIC TOTAL WEIGHT (FILLED WITH WATER) approx. 10 kg/m² plus substructure
PRESSURE STAGE PN 10
MAX. RECOMMENDED OPERATING PRESSURE 4 bar
MAX. ALLOWED HEATING TEMPERATURE 60 °C