prefabricated product| unperforated gypsum board panel with integrated capillary tube mat type OPTIMAT GB 15
OPTIPANEL 15 - CEILING SUBSTRUCTURE

Clina OPTIPANEL 15_Belfius Tower Brussels VIP Offices

Aufbau UK OPTIPANEL_Clina

 

PUSH-LOCK CONNECTIONS

DESIGNATION OPTIPANEL (standard) OPTIPANEL (alternative)
DESCRIPTION with 2 push-lock connections
on the left

with 2 lateral push-lock connections
and 1 middle end cap

ANGULAR POSITION
PUSH-LOCK CONNECTION

PICTOGRAM OPTIPANEL (Standard) Piktogramm Anschlüsse OPTIPANEL (Alternative) Piktogramm Anschlüsse

 

FIELD OF APPLICATION

  • gypsum board ceiling
  • gypsum board wall
  • floating drywall ceiling

TECHNICAL DATA

CAPILLARY TUBE MAT MATERIAL/COLOUR Polypropylene (PP-R) recyclable/blue
MAT DISTRIBUTOR PIPE 20 x 2,0 mm, round
CAPILLARY TUBE OF THE OPTIMAT 4,3 x 0,8 mm
DISTANCE OF THE CAPILLARY TUBES 15 mm centre-to-centre distance
GYPSUM BOARD PANEL unperforated; with pre-drilled pilot holes for fixation (standard)
LENGTH 2.000 mm
WIDTH 625 mm or 1.250 mm
PANEL THICKNESS 12,5 mm
CONNECTION TYPE with 2 push-lock connections 10 mm, angular position 0°
SPECIFIC VOLUME OF WATER 0,320 l/m² capillary tube surface
SPECIFIC TOTAL WEIGHT (FILLED WITH WATER) approx. 11 kg/m² plus substructure
PRESSURE STAGE PN 10
MAX. RECOMMENDED OPERATING PRESSURE 4 bar
MAX. ALLOWED HEATING TEMPERATURE 60 °C