for plaster ceilings and piping
description
Clina Dew Point Sensors register any possible accumulation of condensation at the capillary tube mat or in its immediate surroundings, thereby changing their electric resistance. This resistance change in the sensor is recognised by the room temperature controller TR1 and TR2/3 and causes the control valve to close. It therefore protects the cooling surfaces effectively against damage.
Technical data
Description | dew point sensor for plaster ceilings and piping |
Item No. | TF3 P/R-22 |
Dimensions L x W x H | 70 x 20 x 7 mm (sensor with housing) |
Connecting cable | 2-core cable, length 10 m, 2 x 0,14 mm² (extendable up to approx. 50 m with shielded cable), non-halogen |
Operating voltage | 24 VDC, 24 VAC/50 Hz |
Allowed ambient temperature | 0...50 °C |
Switching point for dew point | approx. 8 MΩ, corresponds to approx. 95% rel. humidity |
Material | housing: plastic; circuit board: gold plated |
|
|
|