capillary tube 4,3 x 0,8 mm | round mat distributor pipe 20 x 2,0 mm

The optimized capillary tube mat with a more robust capillary tube for heating and cooling for all applications where the capillary tube mat is exposed to increased mechanical and/or thermal stress. The OPTIMAT has been developed for "rough" construction site operation, so to speak.

The OPTIMAT is suitable for use in plaster, screed, concrete or in the ground as ground collector and also for integration into metal or drywall panels. The more robust capillary tube provides an increase of safety and thanks to the larger free cross section there is a significantly less pressure loss and better ventilation.

Technical Data

MAT DESIGNATION SB 10 SB 20 GB 20
MATERIAL/COLOUR Polypropylene (PP-R) recyclable/blue Polypropylene (PP-R) recyclable/blue Polypropylene (PP-R) recyclable/blue
MAT DISTRIBURTOR PIPE 20 x 2,0 mm, round 20 x 2,0 mm, round 20 x 2,0 mm, round
CAPILLARY TUBE 4,3 x 0,8 mm 4,3 x 0,8 mm 4,3 x 0,8 mm
DISTANCE A 10 mm 20 mm 20 mm
LENGTH L 600 ‐ 6000 mm in 10 mm steps 600 ‐ 6000 mm in 10 mm steps 600 ‐ 6000 mm in 10 mm steps
WIDTH B as from 150 mm in 20 mm steps as from 150 mm in 20 mm steps as from 150 mm in 20 mm steps
CONNECTION TYPE with open mat distributor pipes/with 2 push-lock connections 10 mm or 15 mm with open mat distributor pipes/with 2 push-lock connections 10 mm or 15 mm with open mat distributor pipes/with 2 push-lock connections 10 mm or 15 mm
SPEC. WEIGHT approx. 870 g/m² capillary tube surface approx. 430 g/m² capillary tube surface approx. 430 g/m² capillary tube surface
SPEC. VOLUME OF WATER 0,570 l/m² capillary tube surface 0,320 l/m² capillary tube surface 0,320 l/m² capillary tube surface
SPEC. TOTAL WEIGHT approx. 1440 g/m² capillary tube surface approx. 750 g/m² capillary tube surface approx. 750 g/m² capillary tube surface
PRESSURE STAGE PN 10 PN 10 PN 10
MAX. RECOMMENDED OPERATING PRESSURE 4 bar 4 bar 4 bar
MAX. ALLOWED HEATING TEMPERATURE 60 °C 60 °C 60 °C
FIELD OF APPLICATION
  • drywall ceiling or wall
  • metal ceiling 
  • concrete ceiling or wall   
  • plaster ceiling or wall 
  • floor
  • facade
  • concrete ceiling or wall 
  • plaster ceiling or wall 
  • floor 
  • soil 
  • facade

Optimat  HEATING AND COOLING MAT  SB 10.00 | 10.11 | 10.20 | 10.02

 

SB 10.00 SB 10.11
with open mat distributor pipes
for welding
with 2 diagonal push-lock connections
OPTIMAT SB 10.00 OPTIMAT SB 10.11

PUSH-LOCK CONNECTIONS

DESIGNATION SB 10.00 SB 10.11 SB 10.20 SB 10.02
DESCRIPTION with open
mat distributor pipes
with 2 diagonal
push-lock connections
with 2
push-lock connections
on the left
with 2
push-lock connections
on the right
PICTOGRAM SB 10.00 Clina push-lock connection pictogram SB 10.11 Clina push-lock connection pictogram SB 10.20 Clina push-lock connection pictogram SB 10.02 Clina push-lock connection pictogram

 

Field of application

  • drywall ceiling or wall| gypsum boards
  • metal ceiling | metal tiles, metal panels

Technical Data

MATERIAL/COLOUR Polypropylene (PP-R) recyclable/blue
MAT DISTRIBUTOR PIPE 20 x 2,0 mm, round
CAPILLARY TUBE 4,3 x 0,8 mm
DISTANCE A 10 mm
LENGTH L 600 ‐ 6000 mm in 10 mm steps
WIDTH B as from 150 mm in 20 mm steps
CONNECTION TYPE with open mat distributor pipes/with 2 push-lock connections 10 mm or 15 mm
SPEC. WEIGHT approx. 870 g/m² capillary tube surface
SPEC. VOLUME OF WATER 0,570 l/m² capillary tube surface
SPEC. TOTAL WEIGHT approx. 1440 g/m² capillary tube surface
PRESSURE STAGE PN 10
MAX. RECOMMENDED OPERATING PRESSURE 4 bar
MAX. ALLOWED HEATING TEMPERATURE 60 °C

 

Optimat  HEATING AND COOLING MAT  SB 20.00 | 20.11 | 20.20 | 20.02

 

SB 20.00 SB 20.11

with open mat distributor pipes
for welding

with 2 diagonal push-lock connections
OPTIMAT SB 20.00 OPTIMAT SB 20.11

PUSH-LOCK CONNECTIONS

DESIGNATION SB 20.00 SB 20.11 SB 20.20 SB 20.02
DESCRIPTION with open
mat distributor pipes
with 2 diagonal
push-lock connections
with 2
push-lock connections
on the left
with 2
push-lock connections
on the right
PICTOGRAM SB 10.00 Clina push-lock connection pictogram SB 10.11 Clina push-lock connection pictogram SB 10.20 Clina push-lock connection pictogram SB 10.02 Clina push-lock connection pictogram

 

Field of application

  • concrete ceiling or concrete wall | prefabricated concrete element, in-situ concrete (ceiling)
  • plaster ceiling or wall | bare concrete, brick wall, gypsum board
  • floor | in screed
  • facade | facade absorber

Technical Data

MATERIAL/COLOUR Polypropylene (PP-R) recyclable/blue
MAT DISTRIBUTOR PIPE 20 x 2,0 mm, round
CAPILLARY TUBE 4,3 x 0,8 mm
DISTANCE A 20 mm
LENGTH L 600 ‐ 6000 mm in 10 mm steps
WIDTH B as from 150 mm in 20 mm steps
CONNECTION TYPE with open mat distributor pipes/with 2 push-lock connections 10 mm or 15 mm
SPEC. WEIGHT approx. 430 g/m² capillary tube surface
SPEC. VOLUME OF WATER 0,320 l/m² capillary tube surface
SPEC. TOTAL WEIGHT approx. 750 g/m² capillary tube surface
PRESSURE STAGE PN 10
MAX. RECOMMENDED OPERATING PRESSURE 4 bar
MAX. ALLOWED HEATING TEMPERATURE 60 °C

OPTIMAT  HEATING AND COOLING MAT  GB 20.00 | 20.11 | 20.20 | 20.02 | GBM 20.11

GB 20.00 GB 20.11 GBM 20.11
with open mat distributor pipes
for welding
with 2 diagonal
push-lock connections
with 2 lateral push-lock connections
and 1 middle end cap
OPTIMAT GB 20.00 OPTIMAT GB 20.11 OPTIMAT GBM 20.11

PUSH-LOCK CONNECTIONS

DESIGNATION GB 20.11 GBM 20.11 GB 20.20 GB 20.02
DESCRIPTION with 2 diagonal
push-lock connections
with 2 lateral
push-lock connections
and 1 middle end cap
with 2
push-lock connections
on the left
with 2
push-lock connections
on the right
PICTOGRAM GB 20.11 Clina push-lock connection pictogram GBM 20.11 Clina push-lock connection pictogram GB 20.20 Clina push-lock connection pictogram GB 20.02 Clina push-lock connection pictogram

Field of application

  • concrete ceiling or concrete wall | prefabricated concrete element, in-situ concrete (ceiling)
  • plaster ceiling or wall | bare concrete, brick wall, gypsum board
  • floor | in screed
  • soil | ground collector
  • facade | facade absorber

Technical Data

MATERIAL/COLOUR Polypropylene (PP-R) recyclable/blue
MAT DISTRIBUTOR PIPE 20 x 2,0 mm, round
CAPILLARY TUBE 4,3 x 0,8 mm
DISTANCE A 20 mm
LENGTH L 600 ‐ 6000 mm in 10 mm steps
WIDTH B as from 150 mm in 20 mm steps
CONNECTION TYPE with open mat distributor pipes/with 2 push-lock connections 10 mm or 15 mm
SPEC. WEIGHT approx. 430 g/m² capillary tube surface
SPEC. VOLUME OF WATER 0,320 l/m² capillary tube surface
SPEC. TOTAL WEIGHT approx. 750 g/m² capillary tube surface
PRESSURE STAGE PN 10
MAX. RECOMMENDED OPERATING PRESSURE 4 bar
MAX. ALLOWED HEATING TEMPERATURE 60 °C